200-Series Distributed Turbine Controls

LCC's 200-Series is a collection of redundant networked distributed modules which are optioned together to form a powerful control and instrumentation system to meet very specific control and I/O requirements in the most demanding of applications.

200-Series Modules may be either VME-P2 size 19-inch rack mounted in control cabinets or stand alone drops in Operator Control Stations or Information terminals.  200-Series Systems consist of collections of 200-Series Modules which may be located about the plant, communicating on the  redundant proprietary (LCCNET-A, LCCNET-B) RS-485 networks.

200-Series Partially Assembled Control Rack Showing VME-P2 Backplane

 

200-Series Module Table List

Module Family Code Description Status*
200-01 Turbine Governors (BFPT, RFPT, Power Gen, Comp) Current
200-02 Analog Input (4 Channel)/Output (4 Channel) Current
200-03 System Parameter & Diagnostic Unit (PDU) Interface Current
200-04 Operator Information Touch Screen (OIT) Interface Current
200-05 Analog Input (8-Channel) Current
200-06 PWM-Driver Output, LPEHC Controller Legacy Only
200-07 Governor Valve Servo Drive Interface Current
200-08 Moderator, LCCNET-A Current
200-09 Moderator, LCCNET-B Current
200-10 Serial Gateway Interface Current
200-11 Combined Moderator LCCNET-A/B Current
200-12 Alstec TSI GAMAP Protocol Interface Legacy Only
200-13 Servo Drive Interface, Serial Current
200-14 TSI Vibration/Phase Input Current
200-15 TSI Thrust/Expansion Input Current
200-16 Plant Simulator Interface Current
200-17 Feedwater Controller Current
200-18 Moderator, LCCNET-A with Power Supply Monitor Current
200-19 Moderator, LCCNET-B with Power Supply Monitor Current
200-20 Operator Control Station Type-CR (Stand Alone) Current
200-21 Operator Control Station Type-LM (Stand Alone) Current
200-22 DCS ModBus RTU Interface Current
200-23 DCS Ethernet Interface Current
200-24 TSI Torsional Vibration Monitor Current
200-25 TSI Thermocouple/RTD Sensor Inputs Current
200-26 Stop Valve Servo Drive Interface Current

*Module Status:    Current = Used in new designs       Legacy Only = Supported for existing systems only.

NOTE:      LCC does not cease to support any design!

 

Typical 200-Series System Applications

Nuclear Main Feedwater Pump Turbines (MFPT)

    For PWR (Pressurized Water Reactor) Nuclear Plants and BWR (Boiling Water Reactor) Nuclear Plants and Fossil Plant Boiler Feed Pump Turbines

DISCUSSION:

Covering General Electric, Westinghouse, DeLaval, and ABB, Alstom, and Siemans turbine driven pumps in the secondary plant cycle steam generator feed in PWRs and Reactor Feed Pumps in BWRs..  These are vital applications not only to plant power output but also to reduce shocks and transients to the plant primary reactor system, therefore REDUNDANT CONTROL MODULE hardware is specified in the 200-Series designs for the utmost in reliability.

SYSTEM CONFIGURATION EXAMPLES

    Two configurations are presented.  Configuration 1A represents a Full Systems Redundant Retrofit or a maximum replacement effort of all ageing and antiquated equipment in the MFPT Control and Instrument range.  Configuration 1B represents a Simplex Governor and Electric Actuator retrofit only.  Because the 200-Series is assembled from the module building blocks any configuration level can be obtained .

1A.    BOM for Full Systems Redundant Retrofit Including Digital Feedwater Control, MFPT Speed, Electric Governor Valve Actuators, Self-Contained Stop Valve Operators, and Turbine Supervisory Instruments

   

Quantity Per MFPT LCC 200-Series Module System Location** Application Notes
3 200-01 Governor SPC 2-of-3 Auctioned Redundant Governors per MFPT.  Each Governor utilizes redundant speed probes. Governors are auctioned by Servo Interface Module in Service.
1 200-17 Feedwater Controller SPC Feedwater Controller for Each MFPT with Tracking Link.  Original FW Control System replaced by one (1) 200-17 Module in each MFPT control system.
1 200-18 LCCNET-A Moderator SPC Includes PS monitoring.
1 200-19 LCCNET-B Moderator LEC Includes PS monitoring.
2 200-07 Governor Valve Servo Interface Module LEC LP and HP Governor Valve Interface Modules which Governor's valve position demands to respective Electric Actuator Servo Drives.  This configuration maintains LP/HP redundancy lacking in the original hydraulic actuator system.
1 200-20 Operator Control Station, CR CR Control Room Operator Control Station.
1 200-21 Operator Control Station, LM LEC Local Manual Operator Control Station
2 200-14 TSI Vibration/Phase LEC Integrated TSI Upgrade, Vibration Sensor Inputs
1 200-24 Thermocouple input LEC Integrated TSI Upgrade, Bearing TC Inputs
1 200-15 Thrust Position LEC Integrated TSI Upgrade, Thrust Sensor Inputs
1 200-10 Serial Gateway Module SPC Serial Data/Alarm System Link to Plant Computer for Historical Data Logs. Includes all control & TSI data.
2 200-25 Stop Valve Servo Interface Module LEC LP and HP Stop Valve Interface Modules which Governor's valve position demands to respective Self Contained Stop Valve Operators.
1 200-03 System Parameter & Diagnostic Unit (PDU) Interface. SPC Interfaces color touch screen for system parameter entry, diagnostics,  and alarm log review.
1 200-04 Operator Information Touch Screen (OIT) Interface. SPC Interfaces color touch screen for control & TSI data display at Operator control room console.
Quantity per MFPT LCC Supplied Additional Components System Location** Application Notes
1 Operator Information Color Touch Screen CR Flat panel graphics data display provides DCS-like features including feedwater, turbine, and TSI mimic displays, data trend plots, and alarm tag board displays.
1 Parameter & Diagnostic Unit Color Touch Screen CR Same hardware as above, but provides an engineering access terminal to the 200-Series to set parameters and perform diagnostic surveillances.
1 LP Governor Servo Drive SDE Vector Servo Drive to operate the LP Electric Actuator.
1 LP GovernorElectric Actuator TUR Exlar Inverse Roller Screw Electric Actuator to position LP Governor Valve Rack, with mounting plate covering previous hydraulic actuator footprint, bracket with trunion bearing, and linkage connecting hardware.
1 LP Governor Actuator Cable Set SDE-TUR Power and Resolver Cables for LP Governor Electric Actuator.
1 HP Governor Servo Drive SDE Vector Servo Drive to operate the HP Governor Electric Actuator.
1 HP Governor Electric Actuator TUR Exlar Inverse Roller Screw Electric Actuator to position HP Governor Valve, with mounting bracket and linkage connecting hardware.
1 HP Governor Actuator Cable Set SDE-TUR Power and Resolver Cables for HP Governor Electric Actuator.
1 LP Stop Valve Actuator TUR Self-Contained Stop Valve Actuator to operate LP Stop Valve with Trip Interface to Turbine Trip System
1 LP Stop Servo Drive SDE Vector Servo Drive to operate the LP Stop Valve Actuator
1 LP Stop Valve Actuator Cable Set SDE-TUR Power and Position Cables for LP Stop Valve Actuator
1 HP Stop Valve Actuator SDE Self-Contained Stop Valve Actuator to operate HP Stop Valve with Trip Interface to Turbine Trip System
1 HP Stop Servo Drive SDE Vector Servo Drive to operate the HP Stop Valve Actuator
1 HP Stop Valve Actuator Cable Set SDE-TUR Power and Position Cables for HP Stop Valve Actuator
2 Active Hall Effect Speed Probes TUR Speed Pickups targeting turbine timing wheel.
2 Speed Probe Transmitters TUR Transmitters for Speed Channel Signals to Governors
4 LCC Tuned Vibration Monitor Transducers TUR Vibration sensors for each turbine and pump bearing.
8 Type-J Dual Thermocouples TUR F&R Thrust Bearing, Journal Bearings 1-4, Oil Drain Temps
2 Thrust Position Probes TUR Redundant Thust Position Proximity Probes
1 Control Networks Cable Set CR-SPC-LEC System Network Cables, LCCNET-A & LCCNET-B
1 Instrumentation Cable Set LEC-TUR TSI System Instrument Cable
1 Signal Processor Cabinet SPC Cabinet housing SPC components.  Located in controlled environment electrical equipment room adjacent to control room.
1 Local Electronics Cabinet LEC Cabinet housing LEC components.  Located within 200 ft. of MFPT. May option self-contained cooling.
1 Servo Drive Enclosure SDE Cabinet housing SDE components.  Located within 75 ft of MFPT.  Self-contained cooling.

** See last three entries for SPC, LEC, and SDE cabinet locations. TUR = Turbine, CR = Control Room.

 

System Block Diagrams, Full System Retrofit

 

 

 

1B.    BOM for Partial Retrofit of MFPT Simplex Speed Governors and Electric Governor Valve Actuators

 

Quantity Per MFPT LCC 200-Series Module System Location** Application Notes
1 200-01 Governor SPC Simplex Governor utilizes redundant speed probes.
1 200-18 LCCNET-A Moderator SPC Includes PS monitoring.
1 200-19 LCCNET-B Moderator LEC Includes PS monitoring.
2 200-07 Governor Valve Servo Interface Module LEC LP and HP Governor Valve Interface Modules which Governor's valve position demands to respective Electric Actuator Servo Drives.  This configuration maintains LP/HP redundancy lacking in the original hydraulic actuator system.
1 200-20 Operator Control Station, CR CR Control Room Operator Control Station.
1 200-21 Operator Control Station, LM LEC Local Manual Operator Control Station
1 200-03 System Parameter & Diagnostic Unit (PDU) Interface. SPC Interfaces color touch screen for system parameter entry, diagnostics,  and alarm log review.
Quantity per MFPT LCC Supplied Additional Components System Location** Application Notes
1 Parameter & Diagnostic Unit Color Touch Screen CR Same hardware as above, but provides an engineering access terminal to the 200-Series to set parameters and perform diagnostic surveillances.
1 LP Governor Servo Drive SDE Vector Servo Drive to operate the LP Electric Actuator.
1 LP Governor Electric Actuator TUR Exlar Inverse Roller Screw Electric Actuator to position LP Governor Valve Rack, with mounting plate covering previous hydraulic actuator footprint, bracket with trunion bearing, and linkage connecting hardware.
1 LP Governor Actuator Cable Set SDE-TUR Power and Resolver Cables for LP Governor Electric Actuator.
1 HP Governor Servo Drive SDE Vector Servo Drive to operate the HP Governor Electric Actuator.
1 HP Governor Electric Actuator TUR Exlar Inverse Roller Screw Electric Actuator to position HP Governor Valve, with mounting bracket and linkage connecting hardware.
1 HP Governor Actuator Cable Set SDE-TUR Power and Resolver Cables for HP Governor Electric Actuator.
2 Active Hall Effect Speed Probes TUR Speed Pickups targeting turbine timing wheel.
2 Speed Probe Transmitters TUR Transmitters for Speed Channel Signals to Governors
1 Control Networks Cable Set CR-SPC-LEC System Network Cables, LCCNET-A & LCCNET-B
1 Instrumentation Cable Set LEC-TUR TSI System Instrument Cable
1 Signal Processor Cabinet SPC Cabinet housing SPC components.  Located in controlled environment electrical equipment room adjacent to control room.
1 Local Electronics Cabinet LEC Cabinet housing LEC components.  Located within 200 ft. of MFPT. May option self-contained cooling.
1 Servo Drive Enclosure SDE Cabinet housing SDE components.  Located within 75 ft of MFPT.  Self-contained cooling.

 

System Block Diagrams, Partial System Retrofit

 

 

 